Customization: | Available |
---|---|
Type: | Termination |
Material: | Silicone Rubber |
Still deciding? Get samples of US$ 10/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Name | Item No. | Suit cables' sectional area (mm2) | Name | Item No. | Suit cables' sectional area (mm2) |
8.7/15kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 25~50 |
VLN-10/3.2 | 70~120 | VLN-10/1.2 | 70~120 | ||
VLN-10/3.3 | 150~240 | VLN-10/1.3 | 150~240 | ||
VLN-10/3.4 | 300~400 | VLN-10/1.4 | 300~400 | ||
VLN-10/3.5 | 500~630 | VLN-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 25~50 |
VLW-10/3.2 | 70~120 | VLW-10/1.2 | 70~120 | ||
VLW-10/3.3 | 150~240 | VLW-10/1.3 | 150~240 | ||
VLW-10/3.4 | 300~400 | VLW-10/1.4 | 300~400 | ||
VLW-10/3.5 | 500~630 | VLW-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Joint | VLJ-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 25~50 |
VLJ-10/3.2 | 70~120 | VLJ-10/1.2 | 70~120 | ||
VLJ-10/3.3 | 150~240 | VLJ-10/1.3 | 150~240 | ||
VLJ-10/3.4 | 300~400 | VLJ-10/1.4 | 300~400 | ||
VLJ-10/3.5 | 500~630 | VLJ-10/1.5 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 39kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 15kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 95kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 15kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 23kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 15kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 95kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 23kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 11kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 11kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |