Customization: | Available |
---|---|
Certification: | Ticw |
Color: | Black / Red / Grey |
Still deciding? Get samples of US$ 30/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Heat-shrinkable cable terminals
It commonly known as heat-shrinkable cable heads, are widely used on the terminals of cross-linked cables or oil-immersed cables with voltage levels of 35KV and below. Compared with the traditional cable accessories, the intermediate connection of the cable has the characteristics of small size, light weight, safety and reliability, and convenient installation.
0.6/1KV-Heat Shrinkable Cable Accessories
Name | Item No. | Suit cables' sectional area (sqmm) | Name | Item No. | Suit cables' sectional area (sqmm) |
0.6/1kV Single Core Heat Shrinkable Termination Kits | VSZ-1/1.0 | 10~16 | 0.6/1kV Single Core Heat Shrinkable Joint | VSJ-1/1.0 | 10~16 |
VSZ-1/1.1 | 25~50 | VSJ-1/1.1 | 25~50 | ||
VSZ-1/1.2 | 70~120 | VSJ-1/1.2 | 70~120 | ||
VSZ-1/1.3 | 150~240 | VSJ-1/1.3 | 150~240 | ||
VSZ-1/1.4 | 300~400 | VSJ-1/1.4 | 300~400 | ||
0.6/1kV 2-cores Heat Shrinkable Termination Kits | VSZ-1/2.0 | 10~16 | 0.6/1kV 2-cores Heat Shrinkable Joint | VSJ-1/2.0 | 10~16 |
VSZ-1/2.1 | 25~50 | VSJ-1/2.1 | 25~50 | ||
VSZ-1/2.2 | 70~120 | VSJ-1/2.2 | 70~120 | ||
VSZ-1/2.3 | 150~240 | VSJ-1/2.3 | 150~240 | ||
VSZ-1/2.4 | 300~400 | VSJ-1/2.4 | 300~400 | ||
0.6/1kV 3-cores Heat Shrinkable Termination Kits | VSZ-1/3.0 | 10~16 | 0.6/1kV 3-cores Heat Shrinkable Joint | VSJ-1/3.0 | 10~16 |
VSZ-1/3.1 | 25~50 | VSJ-1/3.1 | 25~50 | ||
VSZ-1/3.2 | 70~120 | VSJ-1/3.2 | 70~120 | ||
VSZ-1/3.3 | 150~240 | VSJ-1/3.3 | 150~240 | ||
VSZ-1/3.4 | 300~400 | VSJ-1/3.4 | 300~400 | ||
0.6/1kV 4-cores Heat Shrinkable Termination Kits | VSZ-1/4.0 | 10~16 | 0.6/1kV 4-cores Heat Shrinkable Joint | VSJ-1/4.0 | 10~16 |
VSZ-1/4.1 | 25~50 | VSJ-1/4.1 | 25~50 | ||
VSZ-1/4.2 | 70~120 | VSJ-1/4.2 | 70~120 | ||
VSZ-1/4.3 | 150~240 | VSJ-1/4.3 | 150~240 | ||
VSZ-1/4.4 | 300~400 | VSJ-1/4.4 | 300~400 | ||
0.6/1kV 5-cores Heat Shrinkable Termination Kits | VSZ-1/5.0 | 10~16 | 0.6/1kV 5-cores Heat Shrinkable Joint | VSJ-1/5.0 | 10~16 |
VSZ-1/5.1 | 25~50 | VSJ-1/5.1 | 25~50 | ||
VSZ-1/5.2 | 70~120 | VSJ-1/5.2 | 70~120 | ||
VSZ-1/5.3 | 150~240 | VSJ-1/5.3 | 150~240 | ||
VSZ-1/5.4 | 300~400 | VSJ-1/5.4 | 300~400 | ||
Test Project | Test Method | Test Result/Conclusion | |||
1min Power Frequency Voltage (wet state) | 4kV, No breakdown no flashover | No flashover and breakdown of the combined sample under 4kV, 1min wet state | |||
Heating Cycles Voltage Test | Conductor heating to 90-95 ºC, each cycle for 8h, including heating 5h, cooling 3h, a total of three cycles | Complete three load cycle tests as required by the standard | |||
4H Power Frequency Voltage Test | 2.4kV, No breakdown no flashover | No flashover and breakdown of combined specimens |
Name | Item No. | Suit cables' sectional area (sqmm) | Name | Item No. | Suit cables' sectional area (sqmm) |
8.7/15kV Single Core Heat Shrinkable Indoor Termination Kits | VRSN-10/1.1 | 25~50 | 8.7/15kV 3-cores Heat Shrinkable Indoor Termination Kits | VRSN-10/3.1 | 25~50 |
VRSN-10/1.2 | 70~120 | VRSN-10/3.2 | 70~120 | ||
VRSN-10/1.3 | 150~240 | VRSN-10/3.3 | 150~240 | ||
VRSN-10/1.4 | 300~400 | VRSN-10/3.4 | 300~400 | ||
VRSN-10/1.5 | 500~630 | VRSN-10/3.5 | 500~630 | ||
8.7/15kV Single Core Heat Shrinkable Outdoor Termination Kits | VRSW-10/1.1 | 25~50 | 8.7/15kV 3-cores Heat Shrinkable Outdoor Termination Kits | VRSW-10/3.1 | 25~50 |
VRSW-10/1.2 | 70~120 | VRSW-10/3.2 | 70~120 | ||
VRSW-10/1.3 | 150~240 | VRSW-10/3.3 | 150~240 | ||
VRSW-10/1.4 | 300~400 | VRSW-10/3.4 | 300~400 | ||
VRSW-10/1.5 | 500~630 | VRSW-10/3.5 | 500~630 | ||
8.7/15kV Single Core Heat Shrinkable Joint | VRSJ-10/1.1 | 25~50 | 8.7/15kV 3-cores Heat Shrinkable Joint | VRSJ-10/3.1 | 25~50 |
VRSJ-10/1.2 | 70~120 | VRSJ-10/3.2 | 70~120 | ||
VRSJ-10/1.3 | 150~240 | VRSJ-10/3.3 | 150~240 | ||
VRSJ-10/1.4 | 300~400 | VRSJ-10/3.4 | 300~400 | ||
VRSJ-10/1.5 | 500~630 | VRSJ-10/3.5 | 500~630 | ||
Test Project | Standard Requirements | Test Result/Conclusion | |||
1min Power Frequency Voltage (wet state) | 45kV, No breakdown no flashover | No flashover and breakdown of the combined sample under 45kV, 1min wet state | |||
Partial discharge test 13kV devolution power not more than 20PC | 13kV≤20PC | A, B, C three-phase discharge capacity is 2PC under 13kV | |||
Heating Cycles Voltage Test | Conductor heating to 90-95 ºC, each cycle for 8h, including heating 5h, cooling 3h, a total of three cycles | Complete three load cycle tests as required by the standard | |||
Impulse Voltage Test | 105kV positive and negative polarity 10 times each, no flashover and breakdown of the combined specimen | 105kV positive and negative polarity 10 times each, no flashover and breakdown | |||
Negative Polarity DC Voltage Test | 52kV, No breakdown no flashover | 52kV, 15min, No flashover and breakdown of combined specimens | |||
4H Power Frequency Voltage Test | 35kV, No breakdown no flashover | 35kV, 4h, No flashover and breakdown of combined specimens |
Name | Spec. (Single Core) | Spec. (3-cores) | Suit cables' sectional area (sqmm) | ||||
12/20kV | 18/20kV | ||||||
12/20kV Single Core / 3-cores Heat Shrinkable Indoor Termination Kits | VRSN-20/1.1 | VRSN-20/3.1 | 35~70 | ------ | |||
VRSN-20/1.2 | VRSN-20/3.2 | 95~185 | 35~70 | ||||
VRSN-20/1.3 | VRSN-20/3.3 | 240~400 | 95~185 | ||||
VRSN-20/1.4 | VRSN-20/3.4 | 500~630 | 240~400 | ||||
12/20kV Single Core / 3-cores Heat Shrinkable Outdoor Termination Kits | VRSW-20/1.1 | VRSW-20/3.1 | 35~70 | ------ | |||
VRSW-20/1.2 | VRSW-20/3.2 | 95~185 | 35~70 | ||||
VRSW-20/1.3 | VRSW-20/3.3 | 240~400 | 95~185 | ||||
VRSW-20/1.4 | VRSW-20/3.4 | 500~630 | 240~400 | ||||
12/20kV Single Core / 3-cores Heat Shrinkable Joint | VRSJ-20/1.1 | VRSJ-20/3.1 | 35~70 | ------ | |||
VRSJ-20/1.2 | VRSJ-20/3.2 | 95~185 | 35~70 | ||||
VRSJ-20/1.3 | VRSJ-20/3.3 | 240~400 | 95~185 | ||||
VRSJ-20/1.4 | VRSJ-20/3.4 | 500~630 | 240~400 | ||||
Test Project | Standard Requirements | Test Result/Conclusion | |||||
1min Power Frequency Voltage (wet state) | 54kV, No breakdown no flashover | No flashover and breakdown of the combined sample under 54kV, 1min wet state | |||||
Partial discharge test 13kV devolution power not more than 20PC | 20kV≤20PC | A, B, C three-phase discharge capacity is 1pc under 20kV | |||||
Heating Cycles Voltage Test | Conductor heating to 90-95 ºC, each cycle for 8h, including heating 5h, cooling 3h, a total of three cycles | Complete three load cycle tests as required by the standard | |||||
Impulse Voltage Test | 125kV positive and negative polarity 10 times each, no flashover and breakdown of the combined specimen | 125kV positive and negative polarity 10 times each, no flashover and breakdown | |||||
Negative Polarity DC Voltage Test | 156kV, No breakdown no flashover | 156kV, 15min, No flashover and breakdown of combined specimens | |||||
4H Power Frequency Voltage Test | 104kV, No breakdown no flashover | 104kV, 4h, No flashover and breakdown of combined specimens |
Name | Item No. | Suit cables' sectional area (sqmm) | Name | Item No. | Suit cables' sectional area (sqmm) | |
26/35kV Single Core Heat Shrinkable Indoor Termination Kits | VRLN-35/1.1 | 50~95 | 26/35kV 3-cores Heat Shrinkable Indoor Termination Kits | VRLN-35/3.1 | 50~95 | |
VRLN-35/1.2 | 120~185 | VRLN-35/3.2 | 120~185 | |||
VRLN-35/1.3 | 240~400 | VRLN-35/3.3 | 240~400 | |||
VRLN-35/1.4 | 500~630 | VRLN-35/3.4 | 500~630 | |||
26/35kV Single Core Heat Shrinkable Outdoor Termination Kits | VRLW-35/1.1 | 50~95 | 26/35kV 3-cores Heat Shrinkable Outdoor Termination Kits | VRLW-35/3.1 | 50~95 | |
VRLW-35/1.2 | 120~185 | VRLW-35/3.2 | 120~185 | |||
VRLW-35/1.3 | 240~400 | VRLW-35/3.3 | 240~400 | |||
VRLW-35/1.4 | 500~630 | VRLW-35/3.4 | 500~630 | |||
26/35kV Single Core Heat Shrinkable Joint | VRLJ-35/1.1 | 50~95 | 26/35kV 3-cores Heat Shrinkable Joint | VRLJ-35/3.1 | 50~95 | |
VRLJ-35/1.2 | 120~185 | VRLJ-35/3.2 | 120~185 | |||
VRLJ-35/1.3 | 240~400 | VRLJ-35/3.3 | 240~400 | |||
VRLJ-35/1.4 | 500~630 | VRLJ-35/3.4 | 500~630 | |||
Test Project | Standard Requirements | Test Result/Conclusion | ||||
1min Power Frequency Voltage (wet state) | 105kV, No breakdown no flashover | No flashover and breakdown of the combined sample under 105kV, 1min wet state | ||||
Partial discharge test 13kV devolution power not more than 10PC | 39kV≤10PC | A, B, C three-phase discharge capacity is 4pc under 39kV | ||||
Heating Cycles Voltage Test | Conductor heating to 90-95 ºC, each cycle for 8h, including heating 5h, cooling 3h, a total of three cycles | Complete three load cycle tests as required by the standard | ||||
Impulse Voltage Test | 250kV positive and negative polarity 10 times each, no flashover and breakdown of the combined specimen | 250kV positive and negative polarity 10 times each, no flashover and breakdown | ||||
Negative Polarity DC Voltage Test | 156kV, No breakdown no flashover | 156kV, 15min, No flashover and breakdown of combined specimens | ||||
4H Power Frequency Voltage Test | 104kV, No breakdown no flashover | 104kV, 4h, No flashover and breakdown of combined specimens |